  • Q The malfunction of magnetic sensor
    A

    Check wiring

    ■  Correct:Remove magnetic sensor from cylinder, and use a magnet to test the sensor.
    1. Sensor works:the magnetic field of the magnet inside the cylinder is not enough or the sensitivity of magnetic sensor is too weak. Please contact our RD  department.
    2. Sensor doesn't work:Please send back for examination.

    ■  Wrong:Please correct it.

      
  • Q Contact point is unbreakable
    A

    Check whether the magnetic sensor is overloaded.

    ■  No:Check the wire distance between the magnetic sensor and the load is more than 10M or not.
    1. Over 10M:Add an inductor (About 1000uH) to eliminate to capacitor impulse caused by long wiring.
    2. Below 10MPlease send back for examination.

    ■  Yes:
    1. Exchange magnetic sensor with larger rated operating voltage, current, and contact rating.
    2. Use relay or PLC to drive the load indirectly.
  • Q The LED flashes and turns off
    A

    Check whether the loading current is too high.

    ■  Yes:
    1. Exchange magnetic sensor with larger rated operating voltage, current, and contact rating. 《Please refer to the figure below》
    2. Use relay or PLC to drive the load indirectly.
    ■  No:Please send back for examination.

  • Q Magnetic sensor operates twice continuously
    A
    The magnetic field of magnet is too strong or the sensitivity of magnetic sensor is too high.
    Please contact to our RD department.